AFLEX-6300

Graphic Power Quality Analyzer

Availability: In stock
  • Display of Overlapped Voltage and Current Waveform.
  • Maximum Demand (MD in W, KW, MW) with Programmable Period.
  • Harmonics Analysis ( V and I ) to the 50th Order.
  • Display of 25 Harmonics in One Screen with Waveform.
  • Display of waveform with Peak Values (512 Samples / Period), Datalogging of 32, 64, 128 or 256 Points/Cycles.
  • Analysis of Total Harmonics Distortion ( % THD-F ).
  • Graphic Phasor Diagram.
  • Programmable PT (1 to 3000) Ratios.
  • Capture 128 Transient Events ( Time + Cycles + Faults ) with Programmable Threshold(%), Can Also be Reviewed in LCD.
  • 50000 Records with Programmable Interval ( 1 to 6000 seconds).
  • Output of Waveform, Power Parameters and 50 Harmonics at Command.
  • Large Dot Matrix LCD Display with Backlight.
  • Optical Isolated RS-232C Interface.
  • Smart Datalogging to save Battery Power for Long-term Monitoring.
  • Built - in Calendar Clock for Data Logging.
    • Shipping
    • Payments
    • Quantity
    • US$ 988Log in for sale price
    To show price, please join membership and log in.
    Graphic Power Quality Analyzer
    Graphic Power Quality Analyzer
    • Specification
    • Application
    AC Watt ( 45 ~ 65 Hz, PF 0.5 to 1, CT=1 )
    Range
    Resolution
    Accuracy of Readings
    100.0 - 999.9 W
    0.1 W
    2% ± 8 dgts
    1.000 - 9.999 KW
    0.001 KW
    2% ± 8 dgts
    10.00 - 99.99 KW
    0.01 KW
    2% ± 8 dgts
    100.0 - 999.9 KW
    0.1 KW
    2% ± 8 dgts
    1000 - 9999KW
    1 KW
    2% ± 8 dgts

    AC Current (45~65 Hz , True RMS)

    Range
    Range
    Resolution
    Accuracy of Readings
    30 - 300 A
    0.00 - 300 A
    0.1 A
    1 % of range ± 8 dgts
    300 - 999.9 A
    100.0 - 999.9 A
    0.1 A
    1 % of range ± 8 dgts
    1000 - 3000 A
    1000 - 3000 A
    1 A
    1 % of range ± 8 dgts

    Harmonics of ACA in % and Magnitude (1 to 50th order)

    Range
    Resolution
    Accuracy in %
    Resolution
    Accuracy in Magnitude
    10.0 - 300 A
    0.1 %
    ±1.0%
    0.1 A
    ±1.0% of range ± 0.8A
    1000 - 3000 A
    0.1 %
    ±1.0%
    1 A
    ±1.0% of range ± 3 A
    Power Factor (PF)
    Range
    Resolution
    Accuracy of Readings
    0.00 - 1.00
    0.01
    ± 1.5 % ± 8 digits

    Harmonics of AC Voltage in % and Magnitude (1 to 50th order)

    Range
    Resolution
    Accuracy in %
    Resolution
    Accuracy in Magnitude
    50 - 600 V
    0.1 %
    ±0.5%
    0.1V
    ±0.5 % ± 0.5V

    Phase Angle ( Φ )

    Range
    Resolution
    Accuracy of Readings
    -180 ° to 180 ° (0 ° to 360 ° )
    0.1 °
    ± 1 % ± 2 digits

    AC Voltage ( 45 ~ 65 Hz, True RMS)

    Range
    Resolution
    Accuracy of Readings
    3 V - 600 V
    0.1 V
    ± 0.5 % ± 5 dgts

    Total Harmonics Distortion (% THD-F , 1 to 50th order)

    Range
    Resolution
    Accuracy of Readings
    0.0 - 999.9 %
    0.1 %
    ± 0.5 % ± 5 digits

    General Specification:

    Conductor Size 150 mm (approx.)
    Battery Type 1.5 V SUM-3 *2
    Display 128*64 Dot Matrix
    Power Consumption

    10 mA (approx.)

    Auto - Power - Off 15 minutes
    LCD update rate 2 times/sec
    Dimension 130mm(L)*80mm(W)*43mm(H), 5.1"(L)*3.1"(W)*1.7"(H)
    Accessories Test lead*1 pair, Users manual*1, Batteries 1.5V*2
    No. of Sample / Period 512 ( V & A ), 256 (W)
    Operating Temperature -10 ℃ to 50 ℃
    Operating Humidity < 85% RH
    Storage Temperature -20 ℃ to 60 ℃
    Storage Humidity < 75 % RH
    Weight 450g

     

    Related Products