PROVA-6200

Graphic Power Quality Analyzer

Availability: In stock
  • Analysis for Single Phase and Balanced 3 phase system.
  • True RMS Value (V and I).
  • Active Power (K,KW,MW,GW).
  • Apparent (VA,KVA,MVA) and Reactive Power (VAR,KVAR,MVAR).
  • Power Factor (PF), Phase Angle( Φ ).
  • Energy (WH,KWH,KVARH,PFH).
  • Programmable PT(1 to 3000)Ratios.
  • Display of Overlapped Voltage and Current Waveform.
  • Maximum Demand (MD in W,KW,MW) with programmable Period.
  • Harmonic Analysis (V and I) to 50th Order.
  • Display of 25 Harmonics in one screen.
  • Optical Isolated RS-232C Interface.
  • Smart Datalogging to save Battery.
  • Datalogging of 32,64,128 or 256 points/cycles.
  • Analysis of Total Harmonic Distortion (%THD-F).
  • Graphic Phasor Diagram.
  • Capture 128 Transient Events (Time+Cycles+Faults) with Programmable Threshold(%),also can be reviewed in LCD.
  • 50000 Records with Programmable Interval (1 to 6000 seconds).
  • Real-time Output of Waveform, Power Parameters and Harmonics at Command.
  • Large Dot Matrix LCD Display with Backlight.
  • Power for Long-term Monitoring.
  • Built -in Calendar Clock for Data Logging.
    • Shipping
    • Payments
    • Quantity
    • US$ 980Log in for sale price
    To show price, please join membership and log in.
    Graphic Power Quality Analyzer
    Graphic Power Quality Analyzer
    • Specification
    • Application
    AC Current (50 or 60 Hz, Auto Range, True RMS)
    Range
    Resolution
    Accuracy of Reading
    4.0 V - 1500.0 A
    0.01 A
    ± 0.5 % ± 5 dgts

    AC Voltage (50 or 60 Hz, Auto Range, True RMS)

    Range
    Resolution
    Accuracy of Reading
    4.0 - 600.0 V
    0.1 V
    ± 0.5 % ± 5 dgts

    Harmonics of AC Voltage in Percentage and Magniude(1 to 50th order)

    Range
    Resolution
    Accuracy (in%)

    Accuracy 

    (in Magnitude)

    1 – 20 th
    0.1 %
    ± 2 %
    ± 2 % ± 0.5 V
    20 – 50 th
    0.1 %
    4 % of reading ± 2 %
    4 % of reading ± 0.5 V

    Harmonics of AC Current in Percentage and Magnitude (1 to 50th order)

    Range
    Resolution
    Accuracy (in %)

    Accuracy

    (in Magnitude)

    1 – 20 th
    0.1 %
    ± 2 %
    ± 2 % of reading ± 0.4 A
    20 – 50 th
    0.1 %
    4 % of reading ± 2 %
    ± 4 % of reading ± 0.4A

    Power Factor (PF)

    Range
    Resolution
    Accuracy (>20 V and >20 A)
    0.000 - 1.000
    0.001
    ± 0.04

    Phase Angle ( Φ )

    Range
    Resolution
    Accuracy (>20 V and >20 A)
    -180 ° to 180 ° (0 ° to 360 ° )
    0.1 °
    ±1 °

    Total Harmonic Distortion(%THD-F,1 to 50th order)

    Range
    Resolution
    Accuracy (>20 V and >20 A)
    0.0 - 20%
    0.1%
    ± 2 %
    20 - 100%
    0.1%
    ± 6 % of reading ± 1 %
    100 - 999.9%
    0.1%
    ± 10 % of reading ± 1 %

    Crest Factor (C.F.)

    Range
    Resolution
    Accuracy of Readings
    1.00 - 99.99
    0.01
    ± 5 % ± 30 digits

    AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1)

    Range
    Resolution

    Accuracy of Readings

    (>20V and >20A)

    10.0 - 999.9 W
    0.1 W
    ± 1% ± 20 dgts
    1.00 - 9.999 KW
    0.001 KW
    ± 1% ± 20 dgts
    10.00 - 99.99KW
    0.01 KW
    ± 1% ± 20 dgts
    100.0 - 999.9 KW
    0.1 KW
    ± 1% ± 20 dgts
    1000 - 9999 KW
    1 KW
    ± 1% ± 20 dgts

    General Specification:

    Conductor Size 55mm(approx.), 64*24mm(bus bar)
    Battery Type Two 1.5 V SUM-3
    Display 128*64 Dot Matrix
    Power Consumption 10 mA (approx.)
    Auto - Power - Off 30 minutes after power-on
    Update time 2 times/sec. (display)
    No. of Samples per Period 512 (voltage or current),256 (power)
    Operating Temperature -10 ℃ to 50 ℃
    Operating Humidity <85% RH
    Storage temperature -20 ℃ to 60 ℃
    Storage Humidity <75% RH
    Dimension 210 mm (L) * 62 mm (W) * 35.6 mm (H),8.3"(L) * 2.5 "(W) * 1.4"(H)
    Weight Test leads *1 pair, Carrying bag*1, Users manual*1, Batteries 1.5V*2
    Accessories 640g
    Related Products