Power & Harmonics Tester
- Specification
- Application
Electrical Specifications: (23℃±5℃)
AC Watt (Range: 0~1500A)
Range |
Resolution |
Accuracy of Readings |
|
> 20 V and > 20A |
< 20V or < 20A |
||
10.0 – 999.9 W |
0.1W |
±1% ± 20dgts |
±2% ± 40dgts |
1.000 – 9.999 KW |
0.001 KW |
±1% ±20dgts |
±2% ±40dgts |
10.00 – 99.99 KW |
0.01 KW |
±1% ±20dgts |
±2% ±40dgts |
100.0 – 999.9 KW |
0.1 KW |
±1% ±20dgts |
±2% ±40dgts |
1000 – 9999 KW |
1 KW |
±1% ±20dgts |
±2% ±40dgts |
AC Apparent Power (Range: 0~1500A)
Range |
Resolution |
Accuracy of Readings |
|
> 20 V & > 20A |
< 20V or < 20A |
||
10.0 – 999.9 VA |
0.1VA |
±1% ±20dgts |
±2% ±40dgts |
1.000 – 9.999 KVA |
0.001 KVA |
±1% ±20dgts |
±2% ±40dgts |
10.00 – 99.99 KVA |
0.01 KVA |
±1% ±20dgts |
±2% ±40dgts |
100.0 – 999.9 KVA |
0.1 KVA |
±1% ±20dgts |
±2% ±40dgts |
1000 – 9999 KVA |
1 KVA |
±1% ±20dgts |
±2% ±40dgts |
AC Reactive Power (Range: 0~1500A)
Range |
Resolution |
Accuracy of Readings |
|
> 20 V & > 20A |
< 20V or < 20A |
||
10.0 – 999.9 VAR |
0.1VAR |
±2% ±30dgts |
±3% ±40dgts |
1.000 – 9.999 KVAR |
0.001 KVAR |
±2% ±30dgts |
±3% ±40dgts |
10.00 – 99.99 KVAR |
0.01 KVAR |
±2% ±30dgts |
±3% ±40dgts |
100.0 – 999.9 KVAR |
0.1 KVAR |
±2% ±30dgts |
±3% ±40dgts |
1000 – 9999 KVAR |
1 KVAR |
±2% ±30dgts |
±3% ±40dgts |
AC Current (50/60Hz, AutoRange, TRMS, C,F,<4, CT=1, OL Protection AC 2000A)
Range |
Resolution |
Accuracy of Readings |
4.0 – 1500.0 A (for PROVA 6605) |
0.1 A |
±1.0% ± 5dgts |
AC Voltage (50/60Hz, AutoRange, TRMS, C.F.<4, Input Impedance 10 MΩ, Overload Protection AC 800V)
Range |
Resolution |
Accuracy of Readings |
4.0 V – 600.0 V |
0.1 V |
±0.5% ± 5dgts |
Harmonics of AC Voltage in Percentage
Range |
Resolution |
Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 49th |
0.1% |
4% of reading ±2.0% |
50 – 99th |
0.1% |
6% of reading ±2.0% |
Harmonics of AC Voltage in Magnitude
Range |
Resolution |
Accuracy |
1 – 20th |
0.1% |
2% of reading ± 0.5V |
21 – 49th |
0.1% |
4% of reading ±0.5V |
50 – 99th |
0.1% |
6% of reading ±0.5V |
Harmonics of AC Current in Percentage
Range |
Resolution |
Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 49th |
0.1% |
4% of reading ±2.0% |
50 – 99th |
0.1% |
6% of reading ±2.0% |
Harmonics of AC Current in Magnitude
Range |
Resolution |
Accuracy |
1 – 20th |
0.1% |
±2% of reading ±0.4A |
21 – 49th |
0.1% |
±4% of reading ±0.4A |
50 – 99th |
0.1% |
±6% of reading ±0.4A |
Power Factor (PF)
Range |
Resolution |
Accuracy |
|
> 20V and > 20A |
< 20V or < 20A |
||
0.000 – 1.000 |
0.001 |
± 0.04 |
±0.1 |
Phase Angle (Φ, > 20V and > 20A)
Range |
Resolution |
Accuracy |
-180° to 180° |
0.1° |
± 1.5° |
0° to 360° |
0.1° |
± 1.5° |
Total Harmonic Distortion
Range |
Resolution |
Accuracy |
0.0 – 20% |
0.1% |
± 2% |
20.1 – 100% |
0.1% |
± 6% of reading ± 1% |
100.1 – 999.9 % |
0.1% |
± 10% of reading ± 1% |
Peak Value of AC Voltage (peak value > 5V) or AC Current (peak value > 20A)
Range |
Sampling Time |
Accuracy of Reading |
50 Hz |
39 μs |
± 5% ± 30 digits |
60 Hz |
33 μs |
± 5% ± 30 digits |
Resistance (Ω) and Continuity (Beep if less than 50Ω)
Range |
Resolution |
Accuracy |
7.0 – 999.9 Ω |
0.1Ω |
± 5Ω |
1000-1200Ω |
1Ω |
± 5Ω |
Crest Factor (C.F.)of ACV (peak value > 5V) or ACA (peak value > 20A)
Range |
Resolution |
Accuracy of Readings |
1.00 – 99.99 |
0.01 |
± 5% ± 30 digits |
Frequency of ACV (RMS value > 10V) or ACA (RMS value > 30A)
Range |
Resolution |
Accuracy |
45 – 65 |
0.1 |
± 0.2Hz |
General Specifications:
Conductor Size: |
55mm (approx.), 65 x 24mm (bus bar) |
Battery Type: |
two 1.5V SUM-3 |
Display: |
4+4 digits LCD |
Range Selection: |
Auto |
Overload Indication: |
OL |
Power Consumption: |
10 mA(approx.) |
Low battery Indication: |
|
Auto-Power-Off: |
30 minutes after power-on |
Update Time: |
2 times/second (display) |
No. Of Samples per Period |
512 (voltage or current) 256 (power) |
Operating Temperature: |
-10°C to 50°C |
Operating Humidity: |
less than 85% relative |
Altitude: |
up to 2000M |
Storage Temperature: |
-20°C to 60°C |
Storage Humidity: |
less than 75% relative |
Dimension: |
271mm (L) x 112mm (W) x 46mm (H) 10.7" (L) x 4.4" (W) x 1.8" (H) |
Weight: |
647g / 22.8 oz (battery included) |
Accessories: |
test leads x 1 pair Carrying bag x 1 Users manual x 1 Batteries 1.5V x 2 |
Option: |
Alligator clips |